    Standard-Datenblatt  

[Benutzerhandbuch](/products/liquid-cooling-systems/water-heat-exchangers/WL1500/user-manual)

MFG Part Number 1515.00

# WL1500

Legacy Product

## WL Series Liquid Cooling System

 ***Note:** This product has reached end of production. Please use the recommended replacement.  
 Please click the \[Remaining Inventory\] button to see inventory available.  
 The recommended replacement is:  
 MFG Part Number: 1515.01  
 Description: WL1500*  
The WL1500 is a re-circulating liquid to air heat exchanger that offers dependable, compact performance by removing large amounts of heat from a liquid circuit. The coolant is re-circulated using a high pressure pump to assure maximum flow rate. Heat from coolant is absorbed by a radiant heat exchanger and dissipated into the ambient environment using brand name fan. Manual adjustments can be made to control flow switch. Customized features are available, however, MOQ applies.

![Product image](/thermal-wizard/images/lcs/WL1500/WL1500-large.png)

### Eigenschaften

- Kühlung auf Umgebungstemperatur
- Hohe Wärmepumpenkapazität
- Kompakter Formfaktor
- Langlebiger Betrieb

### Anwendungen

- [Kühlung von Teilchenbeschleunigern: Linearbeschleuniger und Zyklotrons](/de/thermal-technical-library/white-papers/cooling-particle-accelerators-linear-accelerators-and-cyclotrons)
- [Kühlung von Halbleiter-Fertigungsanlagen](/de/applications/semiconductor-fabrication-equipment-cooling)
- [Röntgenkühlung in industriellen Scannern](/de/thermal-technical-library/application-notes/x-ray-cooling-industrial-scanners)

![Isometric drawing](/thermal-wizard/images/lcs/WL1500/WL1500-isometric-drawing.png)

### Technical Specifications

**Performance**

Nominal Cooling Capacity

 1,500 W

Nominal Operating Flowrate (60 Hz)

 6.0 L/min @ 6.4 Bar

Nominal Operating Flowrate (50 Hz)

 6.0 L/min @ 6.0 Bar

**Operation**

Coolant

Water or Water/Glycol

Operating Temperature

5°C to 40°C

Storage temperature range (w/o coolant)

-25°C to 70°C

Humidity range

20% to 80%

Storage Humidity range

5% to 95%, non-condensing

Input Voltage

230 VAC

Frequency

50/60 Hz

Current

 &lt; 2.5 Amps

Noise

 &lt; 68 dB(A)

Flow Switch Open

≤ 4 L/min

Maximum Forward Pressure

 7 Bar

**Physical**

Height

481 mm

Length

479 mm

Width

398 mm

Weight

38.5 kg

Coolant Capacity

 3 Liters

Couplings

Press fit (9 mm ID hose)

Features

Applications

Compact design

Medical imaging systems

Reliable operation

Photonics laser systems

Adjustable flow switch

X-Ray scanning systems

Bypass valve protection

Semiconductor fabrication

### Fluid Operating Points

Select Graph

 Qc vs ΔT (Ambient/Inlet) ΔT (Inlet/Outlet) vs Qc Pump Curve (Pressure vs Flow)

 ΔT min: 1.0 °C

 ΔT max: 17 °C

 **100% Water**  
 Cooling Power (Qc) = 1500 Watts  
 Thermal Conductance = 125.3 W/°C  
 ΔT (Ambient-Coolant)* = 12.0 °C  
 ΔT (Outlet-Inlet)** @ 6.0 L/min = 3.6 °C  

 **70/30 Water-Glycol**  
 Cooling Power (Qc) = 1500 Watts  
 Thermal Conductance = 112.0 W/°C  
 ΔT (Ambient-Coolant)* = 13.4 °C  
 ΔT (Outlet-Inlet)** @ 6.0 L/min = 3.8 °C  

 **60/40 Water-Glycol**  
 Cooling Power (Qc) = 1500 Watts  
 Thermal Conductance = 106.3 W/°C  
 ΔT (Ambient-Coolant)* = 14.1 °C  
 ΔT (Outlet-Inlet)** @ 6.0 L/min = 3.9 °C  

 **50/50 Water-Glycol**  
 Cooling Power (Qc) = 1500 Watts  
 Thermal Conductance = 103.3 W/°C  
 ΔT (Ambient-Coolant)* = 14.5 °C  
 ΔT (Outlet-Inlet)** @ 6.0 L/min = 4.1 °C  

\* ΔT (Ambient-Coolant) is the temperature difference between the ambient temperature and the coolant temperature that is at the outlet of the heat exchanger during steady-state operation. This temperature difference would initially be 0 and increase to the steady state value under load. This would also be the temperature at the inlet to the application.

\*\* ΔT (Outlet-Inlet) is the temperature difference between the inlet temperature and the outlet temperature of the application at the nominal coolant flow. More flow (application pressure drop less than nominal) would necessarily mean a smaller ΔT.

### Notes

1. Check coolant level regularly. For optimal cooling performance, coolant level should always be above radiator fins.
2. Hose selection should be of material and thickness to support pressure resistance and coolant type.
3. Manual adjustments can be made to control pressure flow rate.
4. Check air filter and coolant filter periodically for replacement.
5. Multiple cord plug options available to accommodate regional socket outlet requirements. Consult with Laird Technologies on cord plug selection.

Any information furnished by Tark Thermal Solutions and its agents, whether in specifications, data sheets, product catalogues or otherwise, is believed to be (but is not warranted as being) accurate and reliable, is provided for information only and does not form part of any contract with Tark Thermal Solutions. All specifications are subject to change without notice. Tark Thermal Solutions assumes no responsibility and disclaims all liability for losses or damages resulting from use of or reliance on this information. All Tark products are sold subject to the Tark Thermal Solutions Terms and Conditions of sale (including Tark’s limited warranty) in effect from time to time, a copy of which will be furnished upon request.  

 © Copyright 2026 Tark Thermal Solutions, Inc. All rights reserved.

Revision: 00 Date: 06-01-2022

Print Date: 10-21-2026

**Original URL:** https://tark-solutions.com/de/products/liquid-cooling-systems/water-heat-exchangers/WL1500