    標準データシート  

[ユーザーマニュアル](/products/liquid-cooling-systems/water-heat-exchangers/WW3001/user-manual)

MFG Part Number 1104.00

# WW3001

Legacy Product

## WL Series Liquid Cooling System

 ***Note:** This product is not recommended for new designs. Please use the recommended replacement.  
 Please click the \[Legacy Stock\] button to see inventory available.  
 The recommended replacement is:  
 MFG Part Number: 1104.01  
 Description: WW3001*  
The WW3001 uses facility water as a hot side heat dissipation mechanism, which increases the cooling capacity while maintaining form factor. The WW Series system is designed to operate using water as coolant.

![Product image](/thermal-wizard/images/lcs/WW3001/WW3001-large.png)

### 特徴

- 周囲温度への冷却
- 高いヒートポンプ能力
- コンパクトなフォームファクター
- 長寿命動作

### アプリケーション

- [粒子加速器の冷却： 線形加速器とサイクロトロン](/ja/thermal-technical-library/white-papers/cooling-particle-accelerators-linear-accelerators-and-cyclotrons)
- [半導体製造装置の冷却](/ja/applications/semiconductor-fabrication-equipment-cooling)
- [産業用スキャナーにおけるX線冷却](/ja/thermal-technical-library/application-notes/x-ray-cooling-industrial-scanners)

![Isometric drawing](/thermal-wizard/images/lcs/WW3001/WW3001-isometric-drawing.png)

### Technical Specifications

**Performance**

Nominal Cooling Capacity

 3,000 W

Nominal Operating Flowrate (60 Hz)

 5.4 L/min @ 4.0 Bar

Nominal Operating Flowrate (50 Hz)

 5.4 L/min @ 4.0 Bar

**Operation**

Coolant

Water

Operating Temperature

0°C to 40°C

Storage temperature range (w/o coolant)

-20°C to 70°C

Humidity range

10% to 90%

Storage Humidity range

5% to 95%, non-condensing

Input Voltage

230 VAC

Frequency

50/60 Hz

Current

 &lt; 1.8 Amps

Noise

 &lt; 47 dB(A)

Flow Switch Open

≤ 4 L/min

Maximum Forward Pressure

 6.5 Bar

**Physical**

Height

400 mm

Length

450 mm

Width

270 mm

Weight

24 kg

Coolant Capacity

 8.5 Liters

Couplings

Press Fit (9 mm ID hose)

### Fluid Operating Points

Select Graph

 Qc vs ΔT  
ΔT = Coolant Outlet - Facility Water In\* Qc vs ΔT  
ΔT = Coolant Return - Facility Water In\*\* ΔT vs Flow Rate  
ΔT = Coolant Outlet - Facility Water In\* ΔT vs Flow Rate  
ΔT = Coolant Return - Facility Water In\*\* Facilty Pressure Drop  
(Pressure vs Flow) Pump Curve  
(Pressure vs Flow)

\* ΔT (Coolant Outlet - Facility Water In) is the temperature difference between the facility water temperature and the coolant temperature that is at the outlet of the heat exchanger during steady-state operation. This temperature difference would initially be 0 and increase to the steady state value under load. This would also be the temperature at the inlet to the application.

\*\* ΔT (Coolant Return - Facility Water In) is the temperature difference between the facility water temperature and the outlet temperature of the application at the nominal coolant flow. More flow (application pressure drop less than nominal) would necessarily mean a smaller ΔT.

Any information furnished by Tark Thermal Solutions and its agents, whether in specifications, data sheets, product catalogues or otherwise, is believed to be (but is not warranted as being) accurate and reliable, is provided for information only and does not form part of any contract with Tark Thermal Solutions. All specifications are subject to change without notice. Tark Thermal Solutions assumes no responsibility and disclaims all liability for losses or damages resulting from use of or reliance on this information. All Tark products are sold subject to the Tark Thermal Solutions Terms and Conditions of sale (including Tark’s limited warranty) in effect from time to time, a copy of which will be furnished upon request.  

 © Copyright 2026 Tark Thermal Solutions, Inc. All rights reserved.

Revision: 02 Date: 12-08-2023

Print Date: 10-21-2026

**Original URL:** https://tark-solutions.com/ja/products/liquid-cooling-systems/water-heat-exchangers/WW3001