     Standard Datasheet  

[User Manual](/products/liquid-cooling-systems/water-heat-exchangers/LA5000/user-manual)

MFG Part Number 387009381

# LA5000

Legacy Product

## WL Series Liquid Cooling System

 ***Note:** This product is not recommended for new designs. Please use the recommended replacement.  
 Please click the \[Legacy Stock\] button to see inventory available.  
 The recommended replacement is:  
 MFG Part Number: 387009381.02  
 Description: LA5000*  
The LA5000 is a recirculating liquid to air heat exchanger that offers dependable, compact performance by removing large amounts of heat from a liquid circuit. The coolant is re-circulated using a high-pressure pump to assure maximum flow rate. Heat from coolant is absorbed by a radiant heat exchanger and dissipated into the ambient environment using brand name fan. Manual adjustments can be made to control flow switch. Customized features are available, however, MOQ applies.

![Product image](/thermal-wizard/images/lcs/LA5000/LA5000-large.png)

### Features

- Cooling to ambient
- High heat pumping capacity
- Compact form factor
- Long life operation

### Applications

- [Heat Exchangers For Today's Immersion Cooling Systems](/thermal-technical-library/application-notes/heat-exchangers-for-todays-immersion-cooling-systems)
- [Cooling Particle Accelerators: Linear Accelerators and Cyclotrons](/resources/white-papers/cooling-particle-accelerators-linear-accelerators-and-cyclotrons)
- [Semiconductor Fabrication Equipment Cooling](/applications/semiconductor-fabrication-equipment-cooling)
- [X-ray Cooling in Industrial Scanners](/resources/application-notes/x-ray-cooling-industrial-scanners)

![Isometric drawing](/thermal-wizard/images/lcs/LA5000/LA5000-isometric-drawing.png)

### Technical Specifications

**Performance**

Nominal Cooling Capacity

 5,000 W

Nominal Operating Flowrate (60 Hz)

 8.3 L/min @ 6.0 Bar

Nominal Operating Flowrate (50 Hz)

 7.5 L/min @ 6.0 Bar

**Operation**

Coolant

Water or Water/Glycol

Operating Temperature

5°C to 40°C

Storage temperature range (w/o coolant)

-25°C to 70°C

Humidity range

20% to 80%

Storage Humidity range

5% to 95%, non-condensing

Input Voltage

230 VAC

Frequency

50/60 Hz

Current

 &lt; 3.3 Amps

Flow Switch Open

≤ 4 L/min

Maximum Forward Pressure

 10 Bar

Compliance

 ANSI / UL / CSA / IEC EN 61010-1 Edition 3

**Physical**

Height

529 mm

Length

565 mm

Width

468 mm

Weight

40 kg

Coolant Capacity

 6.2 Liters

Couplings

3/8 in NPT

Features

Applications

Cooling to ambient

Cooling Particle Accelerators: Linear Accelerators and Cyclotrons

High heat pumping capacity

Semiconductor Fabrication Equipment Cooling

Compact form factor

X-ray Cooling in Industrial Scanners

Long life operation

### Fluid Operating Points

Select Graph

 Qc vs ΔT (Ambient/Inlet) ΔT (Inlet/Outlet) vs Qc Pump Curve (Pressure vs Flow)

 ΔT min: 0.5 °C

 ΔT max: 16 °C

 **100% Water**  
 Cooling Power (Qc) = 5000 Watts  
 Thermal Conductance = 474.5 W/°C  
 ΔT (Ambient-Coolant)* = 10.5 °C  
 ΔT (Outlet-Inlet)** @ 8.3 L/min = 9.6 °C  

 **70/30 Water-Glycol**  
 Cooling Power (Qc) = 5000 Watts  
 Thermal Conductance = 441.5 W/°C  
 ΔT (Ambient-Coolant)* = 11.3 °C  
 ΔT (Outlet-Inlet)** @ 8.3 L/min = 10.1 °C  

 **60/40 Water-Glycol**  
 Cooling Power (Qc) = 5000 Watts  
 Thermal Conductance = 400.4 W/°C  
 ΔT (Ambient-Coolant)* = 12.5 °C  
 ΔT (Outlet-Inlet)** @ 8.3 L/min = 10.5 °C  

 **50/50 Water-Glycol**  
 Cooling Power (Qc) = 5000 Watts  
 Thermal Conductance = 388.4 W/°C  
 ΔT (Ambient-Coolant)* = 12.9 °C  
 ΔT (Outlet-Inlet)** @ 8.3 L/min = 11.1 °C  

\* ΔT (Ambient-Coolant) is the temperature difference between the ambient temperature and the coolant temperature that is at the outlet of the heat exchanger during steady-state operation. This temperature difference would initially be 0 and increase to the steady state value under load. This would also be the temperature at the inlet to the application.

\*\* ΔT (Outlet-Inlet) is the temperature difference between the inlet temperature and the outlet temperature of the application at the nominal coolant flow. More flow (application pressure drop less than nominal) would necessarily mean a smaller ΔT.

### Notes

1. Check coolant level regularly. For optimal cooling performance, coolant level should always be above radiator fins.
2. Hose selection should be of material and thickness to support pressure resistance and coolant type.
3. Manual adjustments can be made to control pressure and flow rate.
4. Check pump filter and dust on heat exchanger periodically for cleaning.

Any information furnished by Tark Thermal Solutions and its agents, whether in specifications, data sheets, product catalogues or otherwise, is believed to be (but is not warranted as being) accurate and reliable, is provided for information only and does not form part of any contract with Tark Thermal Solutions. All specifications are subject to change without notice. Tark Thermal Solutions assumes no responsibility and disclaims all liability for losses or damages resulting from use of or reliance on this information. All Tark products are sold subject to the Tark Thermal Solutions Terms and Conditions of sale (including Tark’s limited warranty) in effect from time to time, a copy of which will be furnished upon request.  

 © Copyright 2026 Tark Thermal Solutions, Inc. All rights reserved.

Revision: 03 Date: 03-16-2024

Print Date: 10-17-2026