MFG Part Number AA-150-48-44-00-XX

# AA-150-48-44

##  Outdoor Cooler Series Thermoelectric Cooler Assembly

 The AA-150-48-44 is an Air-to-Air thermoelectric cooler assembly that uses impingement flow to transfer heat. It offers dependable compact performance by cooling objects via convection. Heat is absorbed and dissipated through high density heat exchangers equipped with air ducted shrouds and brand name fans. The heat pumping action occurs from custom designed thermoelectric modules that achieve a high coefficient of performance (COP) to minimize power consumption. This model has been designed to pass rigorous Telcordia test requirements conducted by our customers such as earthquake resistance, salt, fog, wind-driven rain, high temperature exposure, and dust contaminants. This is due to the selection of world class components such as brand name fans with the highest degree of environmental protection and lifetime guaranteed waterproof connectors heavy duty anodization on the high-density heat sinks overheat protection and double environmental seals for the thermoelectric modules.

![Product image](/thermal-wizard/images/tea/Outdoor%20Cooler%20Series/AA-150-48-44/AA-150-48-44-large.png)

### Features

- Wide operating temperature range from -40°C to +55°C
- Telcordia GR-487-CORE tested and verified by customers when integrated in telecom outdoor enclosures
- Environmentally friendly solid-state operation
- No compressor or CFC refrigerants
- Optional bi-polar thermostatic control

### Applications

- [Enclosure Cooling](/applications/telecom/enclosure-cooling)
- [Cooling for Mobile Base Stations and Cell Towers](/resources/application-notes/cooling-mobile-base-stations-and-cell-towers)
- [Thermoelectric Cooling for Outdoor Kiosks](/resources/application-notes/thermoelectric-cooling-outdoor-kiosks)
- [Thermal Management Solutions for Beverage Cooling](/resources/application-notes/thermal-management-solutions-beverage-cooling)
- [Energy Storage Systems](/resources/application-notes/energy-storage-systems)

![Isometric drawing](/thermal-wizard/images/tea/Outdoor%20Cooler%20Series/AA-150-48-44/AA-150-48-44-isometric-drawing.png) ![](/thermal-wizard/images/tea/CE-ROHS.png)

### Specifications

Heat Transfer Mechanism, Cold Side

Air - Forced Convection

Heat Transfer Mechanism, Hot Side

Air - Forced Convection

Temperature Range (External Ambient)1

-40°C to 55°C

Temperature Range (Internal Enclosure)

-20°C to 55°C

Supply Voltage

48.0 VDC nominal / 56.0 VDC maximum

Current Draw

3.9 A running / 5.0 A startup

Power Supply

190.0 Watts

Performance Tolerance

10%

Hi-Pot Testing

707 VDC

Fan MTBF

70000 hours

Heating2

150 W

Over-Temp Thermostat (Hot and Cold Side Heat Sink)

80°C ± 3°C

Sound Level (1 m distance)

58 dBA

Degree of Protection (Unit Internal Side)

IP54

Degree of Protection (Unit External Side)3

IP54

Connector Type (On Unit)

AMP part number: 350777-1, 794269, 350547-6, 794270-1

Connector Type (Mating Side)

AMP part number: 350778-1, 350550-6, 794270-1

Weight

5.10 kg

Panel Mounting

Through

### Mounting Hole Location

![Mounting Hole Location](/thermal-wizard/images/tea/Outdoor%20Cooler%20Series/AA-150-48-44/AA-150-48-44-mounting.png)

### Wiring Schematic

![Wiring Schematic](/thermal-wizard/images/tea/Outdoor%20Cooler%20Series/AA-150-48-44/AA-150-48-44-wiring-schematic.png)

### Electrical and Thermal Performance

**Optimum COP**  
 Cooling Power (Qc) = 36.95 Watts  
 TEM Voltage = 28.33 Volts  
 TEM Current = 1.83 Amps  
 TEM COP = 0.71  
 Power Supply = 51.8 Watts  
 Power Dissipated (Qh) = 88.76 Watts  
 Fan Voltage = 48.0 Volts  
 Fan Current = 1.1 Amps  

**Maximum Qc**  
 Cooling Power (Qc) = 89.21 Watts  
 TEM Voltage = 56.14 Volts  
 TEM Current = 3.79 Amps  
 TEM COP = 0.42  
 Power Supply = 212.8 Watts  
 Power Dissipated (Qh) = 302.0 Watts  
 Fan Voltage = 48.0 Volts  
 Fan Current = 1.1 Amps  

#### Default Calculated Operating Conditions

##### Electrical Operating Point

- TEC Voltage: 48 V
- TEC Current: 3.23 A
- Cooling Power (Qc): 78.9 W
- Power Supply: 154.95 W
- TEC COP: 0.51
- Power Dissipated (Qh): 233.85 W
- Fan Voltage: 48 V
- Fan Current: 1.1 A

##### Thermal Operating Conditions

Mode: Cooling

- Ambient High Temperature: 35 °C
- Control Temperature: 20 °C
- Cooling ΔT: 15 °C

### Notes

1 Controller function shall not operate the external fan during heating mode.

2 Heating capacity is rated at external temperature of -40°C, nominal voltage, and dT = -45°C.

3 The highest environmental protection level NEMA 4 (IP55) requires an external shroud and is defined as the protection level for the enclosure.

Any information furnished by Tark Thermal Solutions and its agents, whether in specifications, data sheets, product catalogues or otherwise, is believed to be (but is not warranted as being) accurate and reliable, is provided for information only and does not form part of any contract with Tark Thermal Solutions. All specifications are subject to change without notice. Tark Thermal Solutions assumes no responsibility and disclaims all liability for losses or damages resulting from use of or reliance on this information. All Tark products are sold subject to the Tark Thermal Solutions Terms and Conditions of sale (including Tark’s limited warranty) in effect from time to time, a copy of which will be furnished upon request.  

 © Copyright 2026 Tark Thermal Solutions, Inc. All rights reserved.

Revision: 01 Date: 03-12-2026

Print Date: 10-21-2026

**Original URL:** https://tark-solutions.com/products/thermoelectric-cooler-assemblies/peltier-air-conditioners/AA-150-48-44